| Power Range | 630 kVA – 31,500 kVA (standard); custom ratings on request |
|---|---|
| Max Voltage | Up to 36 kV |
| Technology | Oil Immersed |
| Standard | IEC 60076 / EN 50588 |
| Cooling | ONAN / ONAF |
| Impedance | 4 – 12.5 % |
| BIL (Lightning) | Up to 200 kV |
| Temperature Rise | 65 K / 60 K |
| Weight Range | 2.5 – 65 t |
| Losses | EU 548/2014 Tier 2 compliant; guaranteed values per unit |
| Short-Circuit Std. | IEC 60076-5 |
| Conducting Material | Copper or Aluminium (customer choice) |
| HV Coil Construction | Precision oil-paper insulated winding; layer or disc winding |
| LV Coil Construction | Helical or layer winding; optimised for distribution duty |
| Insulation System | Mineral oil standard; synthetic ester / silicone on request |
| Tank / Enclosure | Corrugated tank (standard); radiator tank; hermetically sealed or conservator; full accessories |
| Tap Changer | NLTC ±2×2.5 % standard; OLTC per IEC 60214 on request |
| Climate Class | Per IEC 60076; arctic option on request |
| Ambient Class | Per IEC 60076 |
| Fire Class | Oil-immersed; fire-retardant ester fluid on request |
| Certifications & Standards | IEC 60076; EN 50588; ISO 9001:2015; EU 548/2014 Tier 2; GOST on request |
| Ecodesign Level | EU 548/2014 Tier 2 compliant |
| Offshore Classification | On request |
| GOST Available | Yes – on request |
| Key Applications | Urban and rural MV/LV networks; grid reinforcement; industrial power supply; renewable energy grid-tie; substation upgrades |
| Industries Served | Energy utilities; grid operators; industrial plants; urban infrastructure; renewable energy |
| Typical Delivery | ~3 months (standard range); express delivery for network recovery |